The mirrors fog before anyone gets in. The ceiling above the far lane has a ring of paint that has lifted twice. Someone has wiped the window frames so often that the seals have gone. The indoor pool dehumidifier has been running since the day the building opened, and the room still smells of chlorine.
None of that is a dehumidifier fault. In most pool halls it is a sizing fault, and the sizing went wrong months before anyone bought a machine — in the first design meeting, where three numbers were written down as comfort targets and never looked at again.
Almost every guide to indoor pool dehumidifier sizing starts with water surface area. That is correct and it is not enough. Surface area sets the base load. Three setpoints decide how much of that load you actually remove, and each one moves the number by more than most people expect.
Three setpoints decide what your indoor pool dehumidifier must do
Every pool-hall evaporation calculation — ASHRAE, Carrier, any manufacturer’s spreadsheet — has the same shape:
moisture removed = 0.1 × surface area (ft²) × (vapour pressure at water temperature − vapour pressure in the room air) × activity factor
The surface area is fixed by the architect. The activity factor is fixed by what the pool is used for. Everything else in that line is a setpoint someone chose:
| Setpoint | Who sets it | What moving it does |
| Room air temperature | HVAC designer, then the operator | Lower it and evaporation rises |
| Relative humidity | Often “wherever it settles” | Drop it and evaporation rises fast |
| Air velocity over the water | Diffuser layout, decided once, rarely checked | Aim air at the water and the load jumps |
The rest of this article puts a number on each one, then shows what the three add up to on a real pool. The removal happens at a refrigerated coil; the mechanics are set out in how a dehumidifier works
Why the air has to sit above the water
The first thing to get right is the relationship between water temperature and air temperature, because it is the one setpoint that looks like a comfort preference and is actually a load multiplier.
Indoor pool air should run 1–2 °C above the pool water temperature. Not equal, not below. Four independent sources agree:
- FINArequires air at least 2 °C above water
- The European Commission SAVEprogramme puts the optimum at water +1 to +2 °C
- ASHRAErecommends 2–4 °F above water, capped at 86 °F for occupant comfort
- China’s code for sports building design (JGJ 31)gives 1–2 °C, and states the reason plainly: a bather leaving water that is warmer than the air feels cold
That is why people notice this number. Step out of a 29 °C pool into 26 °C air and you feel a chill that has nothing to do with the water — the air is pulling heat off wet skin faster than the water was.
The same rule does three jobs at once. It keeps bathers comfortable, it limits evaporation, and it keeps the dew point of the room air below the temperature of the windows and structural steel. Get it wrong in the other direction — air too warm — and you trade comfort for a smaller load while pushing the room toward condensation on every cold surface.
Raise the water four degrees and the load goes up a third
Here is why the relationship matters more than it looks. Published natatorium design guidance contains a worked example worth repeating, because the arithmetic is uncomfortable:
A 3,500 ft² pool hall designed for 82 °F water and 84 °F air, at 55 % relative humidity, has an evaporation load of about 159 lb/h. Raise the water to 86 °F and change nothing else: 211 lb/h. That is 33 % more moisture from a 4 °F change in water temperature.
Run the same calculation through the ASHRAE form above and you get 159.5 and 212.4 lb/h. Method and published example agree to within a pound, so the load really does move that much.
This is not hypothetical. Average commercial pool water temperatures rose from roughly 82 °F to 86 °F between 2003 and 2013, driven by learn-to-swim classes for young children and vertical aquatics for older adults. A plant designed in 2010 for 82 °F water is now running a dehumidifier sized for a load 30 % smaller than the one it faces.
Two practical consequences:
- Ask what water temperature the system was sized for, and what it runs at now.If those differ, the machine is undersized regardless of what the schedule says.
- Every degree counts.Evaporation rises roughly 3–5 % per 1 °F, exponentially, so the penalty grows as the water warms.
The air blowing across the water is worth another 40 per cent
The second setpoint is air velocity, most often ruined by a well-meaning duct layout.
The instinct is to blow air at the water. Exactly backwards. Supply air should be directed at exterior walls, glazing and the perimeter — the surfaces that condense — not at the pool surface.
The published guidance is blunt. Raising airflow across the water from 30 ft/min to 125 ft/min increases the evaporative load by 40 % on the same pool at the same temperatures. Thirty feet per minute is about 0.15 m/s; 125 ft/min is about 0.64 m/s, a normal diffuser discharge aimed the wrong way.
An engineer who sizes correctly using the standard equation, and then lets the contractor point the grilles at the pool, has delivered a machine that is 40 % too small and will never catch up.
Keep air velocity over the water below 30 ft/min, and put the supply air on the walls.
Why 40 per cent relative humidity is as wrong as 80
The third setpoint is the one people adjust without thinking, because a number on a controller feels like a preference.
ASHRAE puts natatorium relative humidity at 50–60 %. China’s sports building code allows up to 70 % in service and is explicit that it should not exceed 75 %. Both limits exist for structural reasons, not comfort ones.
Push the room dry and the load climbs steeply. On the worked example later in this article, taking the room from 60 % to 40 % relative humidity raises the moisture load by about 69 % — same machine, same pool, a third more water to remove.
Push it wet and the load falls, which looks like a saving and is not. At 75 % relative humidity the same pool evaporates about half as much, but the room dew point climbs toward the temperature of every cold surface in the building. That is when paint lifts, steel deck screws rust, insulation saturates and mould establishes itself inside cavities where nobody can reach it. The saving on the dehumidifier is repaid several times over in remediation.
Sixty per cent, held steadily, is the target. Not 40, not 75.
The load is four things, and only one of them is the pool
Pool surface evaporation is the biggest single item, but it is not the whole load, and treating it as the whole load is where small pools in hot climates go wrong.
The four components:
- Water surface evaporation— the main term, computed from the equation above
- Wetted deck— splash-out on the surround, roughly the first 1.5–2 m out from the pool edge, contributing a further 5–15 % in active pools
- Occupants— bathers and staff, small per person but never zero in a commercial pool
- Outdoor air— the term that decides projects in South-East Asia, and the one most often left out
That last term deserves its own paragraph: in Vietnam, Thailand, Indonesia and the Philippines it can rival the pool itself.
ASHRAE 62.1 calls for around 0.48 cfm of outdoor air per square foot of pool and deck area in a natatorium — a high figure, and a deliberate one, because the air has to dilute chloramines. Chloramines, and especially trichloramine, are what people are actually smelling when they say a pool “smells of chlorine”. They form from chlorine reacting with sweat, urine and skin particles, they irritate eyes and airways, and they accumulate in the air above an active pool. Fresh air is the control.
Now run the numbers on a humid day. Outdoor air at 33 °C and 80 % relative humidity carries about 25.7 g of water per kg of dry air. Room air at 30 °C and 60 % carries about 16.0 g/kg. The difference is around 9.7 g/kg that has to be removed from every kilogram of fresh air brought in.
For a 120 m² pool with 1,300 ft² of pool and deck area, the code requirement works out to roughly 620 cfm, about 1,050 m³/h. At 1.2 kg/m³ that is about 1,210 kg of air per hour, carrying roughly 11.7 kg of water per hour that the dehumidifier has to take out.
The pool surface, on the same day, produces about 17 kg/h.
So the fresh air alone is worth roughly two-thirds of the pool load. Size on the water surface and you have designed a machine for 60 % of the job.
What a realistic number looks like
Put the three setpoints and the four loads together on a hotel pool and the arithmetic becomes concrete.
The pool: 15 m × 8 m, so 120 m² of water. Water at 28 °C, room at 30 °C — the 2 °C offset the standards ask for. Relative humidity 60 %. A hotel pool, so activity factor 0.8.
Step one, the water surface. Using the ASHRAE form: 1,292 ft² × 0.365 in.Hg of vapour pressure difference × 0.8 activity factor, at the 0.1 coefficient, gives 37.7 lb/h. That is 17.1 kg/h, or about 410 litres a day.
Cross-check. The rule of thumb in pool engineering is 4 litres per m² of water surface per day, which on 120 m² predicts 480 litres a day. Two independent routes, 410 and 480 — within 15 %, which is as close as this kind of estimate gets. Take the higher figure and move on.
Step two, add the outdoor air. As above, roughly 11.7 kg/h in a hot humid climate. Running total: about 28.8 kg/h, or roughly 690 litres a day.
Step three, allow for the rest. Wetted deck and occupants add a few per cent. Design practice is to size at 70–80 % of rated capacity, for headroom on a full pool and for a coil five years in service. That pushes selection to the 700–900 litre/day band.
That is the number that matters, and it is nearly double what the surface-area rule alone would have told you.
One caveat: a nominal rating taken at 30 °C and 80 % relative humidity does not transfer to a room held at 60 %. Less room humidity means a smaller vapour pressure difference at the coil and less condensate per hour. Ask for capacity at your design condition, then apply the margin.
Why a residential dehumidifier cannot do this job
A basement dehumidifier is not a small version of what a pool hall needs. Three differences matter.
Duty cycle. A basement dehumidifier runs until the basement is dry, then stops. A pool hall never stops evaporating. The machine runs continuously, all year, and its compressor is expected to survive that. Residential units are not built for continuous duty, and the warranty terms usually say so.
Capacity. Residential units are rated in pints per day — a 150-pint unit is about 71 litres a day. The hotel pool above needs 690. You would be installing ten machines, ten drains, and ten points of failure. The commercial range starts around 50 litres a day and steps up from there for a reason.
Corrosion. This is the one that decides the project.
Chlorine, corrosion and the question to ask every supplier
Chlorinated pool air is one of the most aggressive indoor environments a building can put equipment in. Chloramines attack copper, aluminium and ordinary steel, and a coil that lasts fifteen years in an office lasts a fraction of that above a pool.
What good equipment does about it:
- Coated coils— epoxy or equivalent on the fin pack, so copper and aluminium are not directly exposed
- Non-metallic drain pans— stainless or polymer, because a condensate pan is permanently wet and permanently in chlorinated air
- Coated or stainless cabinet and fan components, with access for cleaning, because a coil that cannot be washed cannot be kept alive
So the question to ask every supplier, in writing, before comparing price:
What is the coil coating, what is the drain pan material, and what corrosion protection is on the fan and cabinet?
A supplier who answers specifically has built for pools before. One who says “it is fine, we sell many to pools” has not answered.
What to send before anyone quotes you
Capacity cannot be read off a floor plan. To size properly, a supplier needs:
- Water surface area in m²— not the room area, the water
- Water temperature— the design figure and the temperature it actually runs at
- Room air temperature and relative humidityyou intend to hold
- Pool type and peak bather count— private, hotel, school, therapy, competition
- Any water features— slides, fountains, jacuzzi, spa. Each one raises the load and the activity factor
- Outdoor design condition— summer dry bulb and humidity, and whether the space is mechanically ventilated or sealed
- Ceiling height and whether a plant room exists— this decides between a ducted unit, a floor-standing unit and a ceiling cassette, a trade-off covered in ceiling-mounted versus floor-standing dehumidifiers
Send those seven and a capacity can be calculated with a defensible number behind it. Send a photo of the room and the answer will be a guess.
FAQ
How do I calculate the dehumidifier capacity for an indoor pool?
Multiply water surface area in square feet by the vapour pressure difference between water surface and room air in inches of mercury, by 0.1, then by the pool’s activity factor. That is the surface load in lb/h. Add wetted deck, occupants and outdoor air, then select at 70–80 % of rated capacity. In metric, the 4 litres per m² per day rule lands within about 15 %.
What relative humidity should an indoor pool room be kept at?
50–60 %, held steadily. Below that the pool evaporates much faster and bathers feel cold; above it the dew point climbs toward the temperature of windows, steel and insulation, and condensation starts inside the structure. Sixty per cent is the working target.
Should the pool hall air be warmer or colder than the water?
Warmer, by 1–2 °C. FINA, ASHRAE, the EU SAVE programme and China’s sports building code all converge on this. It cuts evaporation, keeps bathers comfortable leaving the water, and holds the room dew point away from cold surfaces.
Can I use a normal industrial dehumidifier for a pool?
An industrial refrigerant dehumidifier has the right capacity range and the right operating principle, because warm humid air is exactly what a refrigeration coil removes water from most efficiently. What decides whether it survives is corrosion protection: coil coating, drain pan material, cabinet finish. Ask for those three in writing.
Why does the pool hall still smell of chlorine if the humidity is controlled?
Because the smell is chloramines, not chlorine, and humidity control does not remove them. Trichloramine forms when chlorine meets sweat and skin particles and accumulates in the air. It is diluted with outdoor air — ASHRAE 62.1 asks for around 0.48 cfm per square foot in a natatorium. Humidity control protects the building; ventilation protects the air.
Is a desiccant dehumidifier better for a pool?
Usually not. Desiccant rotors earn their place at very low dew points or in cold air. A pool hall is the opposite case — warm and wet — which is the efficient range of a refrigeration coil. Desiccant comes into play only where the space is unheated or the climate is cold.
Tell us the pool, not the room
Send the seven items above through the contact form and we will come back with a capacity, the reasoning, and the equipment that fits. We build refrigerant dehumidifiers from 168 to 960 litres a day, and constant temperature and humidity units that hold 18–30 °C and 40–70 % relative humidity — enough for most pool halls up to competition size. Where a project needs a dedicated natatorium package with pool-water heat recovery, we will say so rather than bend a different machine into the job.